Inox-Maxi SSC1 | Model | 500 | 800 | 1000 | 1300 | 1500 | 2000 |
---|---|---|---|---|---|---|---|
Storage capacity | Litres | 503 | 759 | 902 | 1272 | 1398 | 2018 |
Output at primary temp 80/60°C | kW | 40.7 | 48.2 | 62 | 69 | 69 | 75.9 |
Continuous DHW delivery ΔT 50°C with primary temp 80/60°C | Litres/hour | 699 | 828 | 1067 | 1186 | 1186 | 1305 |
Continuous DHW delivery ΔT 50°C with primary temp 80/70°C | Litres | 773 | 932 | 1187 | 1314 | 1314 | 1442 |
Standby heat loss (DHW temperature 65°C) | kW/24hr | 2.3 | 2.7 | 2.8 | 3.5 | 3.8 | 4.3 |
Energy class | C | C | C | C | C | C | |
Width | mm | 750 | 1010 | 1020 | 1170 | 1220 | 1470 |
Height | mm | 1790 | 1943 | 2192 | 2212 | 2197 | 2070 |
Weight empty/full | kg | 100/603 | 160/919 | 185/1087 | 250/1522 | 262/1660 | 377/1470 |